Installation Manual
35
ENGLISH
How to Set E.S.P?
Installer Setting - Static Pressure Step Setting
This function is applied to only duct type. Setting this in other cases will cause malfunction.
This function is only available on some models.
This is the function that static pressure of the product is divided in 11 steps for setting.
Select the code value and set value for each function using
F G
button.
Press and hold
B
button for more than 3 seconds to enter the installer settings mode.
- If pressing only once briefly, it will enter the user settings mode.
Make sure to press and hold for more than 3 seconds.
Press
B
button repeatedly to move to the Settings for Static Pressure Step in the menu as below.
Press
K
button to save the setting.
Press
L
button to exit.
h
If no button is selected for about 25 seconds after setup, it exits the setup mode automatically.
h
If
K
button is not selected before you exit, the changes will not apply.
Code value
Set value
❈
Set value for static pressure step
00 : use static pressure(code 06) set value
01~ 11 : static pressure step (code 32) set value
• Static Pressure (Code 06) setting will not be used if Static Pressure Step (Code 32)setting is
being used.
• For the static pressure value for each step, refer to the indoor unit in the product manual.
1,MFL67939921,영영 2018. 8. 2. 영영 1:41 Page 35