40
How to Set E.S.P?
Model
Step
CMM
[m
3
/
min]
Static Pressure[mmAq(Pa)]
6(59)
7(69)
8(78)
9(88) 10(98) 12(118) 13(127) 14(137) 15(147) 16(157) 18(176)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10
32:11
ABNW70GB9A0
LOW
60
70
72
74
76
78
81
82
85
86
88
91
MID
65
74
76
78
80
82
85
86
89
90
92
95
HIGH
70
78
80
82
84
86
90
91
93
94
96
99
Model
Step
CMM
[m
3
/
min]
Static Pressure[mmAq(Pa)]
6(59)
7(69)
8(78)
9(88) 10(98) 12(118) 13(127) 14(137) 15(147) 16(157) 18(176)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10
32:11
ABNW85GB9A0
LOW
64
74
75
76
78
79
82
84
86
89
91
95
MID
72
78
79
80
82
83
87
89
91
94
96
100
HIGH
80
82
84
86
88
90
93
95
97
100
101
105
Ceiling Concealed Duct – High static
Table 4
NOTE
1. Be sure to set the value refering table 4. Unexpected set value will cause mal-function.
2. Table 4 is based at 230 V. According to the fluctuation of voltage, air flow rate varies.
3. Factory Set(External Static Pressure) each Model
* If it is zero static pressure, please set value below Maximum value.
Model
Maximum value
ABNW85GB9A0
ABNW70GB9A0
105
Model
Factory set (E.S.P.) mmAq(Pa)
ABNW85GB9A0
ABNW70GB9A0
13 (127)
1,MFL67939921,영영 2018. 8. 2. 영영 1:41 Page 40