1. Multiple piping type MULTI F
8
_ Heat Pump
50Hz/R410A
Part 2 Product data_Outdoor units
Models : A2UW14GFA0 [MU2M15 UL2]
Cooling
Heating
Note :
1. Cooling Capacity is based on : indoor temp.27°CDB, 19°CWB
; outdoor temp. 35°CDB, 24°CWB
2. Heating Capacity is based on : indoor temp.20°CDB, 15°CWB
; outdoor temp. 7°CDB, 6°CWB
3. Maximum total capacity index of connected indoor units is 21 kBtu/h.
4. At least two indoor units should be connected to outdoor unit.
5. Total capacity of indoor units connected should be minimum 40% of outdoor unit rated capacity.
5
-
5
1.5 -
3,000
0.9
5,000
1.5
6,000
1.8
290
480
600
1UNIT
7
-
7
2.1 -
4,200
1.2
7,000
2.1
8,400
2.5
320
520
620
9
-
9
2.6 -
5,400
1.6
9,000
2.6
10,800
3.2
400
660
850
12
-
12
3.5 -
7,200
2.1
12,000
3.5
14,400
4.2
530
880
1,220
5
5
10
1.5 1.5
6,000
1.8
10,000
2.9
11,500
3.4
480 800
1,090
5
7
12
1.5 2.1
7,200
2.1
12,000
3.5
13,800
4.0
530 880
1,220
5
9
14
1.5 2.6
8,400
2.5
14,000
4.1
16,100
4.7
620
1,020
1,450
5
12
17
1.4 3.3
9,600
2.8
16,000
4.7
18,400
5.4
770
1,260
1,630
2 UNIT
7
7
14
2.1
2.1
8,400
2.5
14,000
4.1
16,100
4.7
620
1,020 1,450
7
9
16
2.1 2.6
9,600
2.8
16,000
4.7
18,400
5.4
770
1,260
1,630
7
12
19
1.7 3.0
9,600
2.8
16,000
4.7
18,400
5.4
770
1,260
1,630
9
9
18
2.3 2.3
9,600
2.8
16,000
4.7
18,400
5.4
770
1,260
1,630
9
12
21
2.0 2.7
9,600
2.8
16,000
4.7
18,400
5.4
770
1,260
1,630
Combination
(kBtu/h)
Each capacity
(kW)
Total Capacity (kW)
Cooling
Min
Rated
Max
Input
(W)
Unit-A Unit-B
Total
Unit-A Unit-B
Btu/h
kW
Btu/h
kW
Btu/h
kW
Min
Rated
Max
Operation
5
-
5
1.6 -
3,300 1.0
5,500 1.6
6,000 1.8
290 480 600
1 UNIT
7
-
7
2.5 -
5,100 1.5
8,400 2.5
9,200 2.7
340 560 710
9
-
9
3.2 -
6,500
1.9
10,800
3.2
11,800
3.5
420
700
890
12
-
12
3.9 -
8,000
2.3
13,200
3.9
14,500
4.2
520
860
1,120
5
5
10
1.6 1.6
6,600
1.9
11,000
3.2
12,100
3.5
450 740 940
5
7
12
1.6 2.3
8,000
2.3
13,200
3.9
14,500
4.2
520 860
1,090
5
9
14
1.7 3.0
9,600
2.8
16,000
4.7
17,200
5.0
650
1,080
1,390
5
12
17
1.6 3.7 10,800 3.2
18,000 5.3
19,400 5.7
780 1,280 1,660
2 UNIT
7
7
14
2.3
2.3
9,600
2.8
16,000
4.7
17,200
5.0
650
1,080
1,390
7
9
16
2.3 3.0 10,800 3.2
18,000 5.3
19,400 5.7
780 1,280 1,660
7
12
19
1.9 3.3 10,800 3.2
18,000 5.3
19,400 5.7
780 1,280 1,660
9
9
18
2.6 2.6 10,800 3.2
18,000 5.3
19,400 5.7
780 1,280 1,660
9
12
21
2.3 3.0 10,800 3.2
18,000 5.3
19,400 5.7
780 1,280 1,660
Combination
(kBtu/h)
Each capacity
(kW)
Total Capacity (kW)
Heating
Min
Rated
Max
Input
(W)
Unit-A Unit-B
Total
Unit-A Unit-B
Btu/h
kW
Btu/h
kW
Btu/h
kW
Min
Rated
Max
Operation
1.4 Combination table