3. Distributor type MULTI F DX (3 phase)
25
_
Heat pump 50Hz/R410A
Part 2 Product data_Outdoor units
Notes:
1. Capacities are based on the following conditions.
Main Piping Length 5m, Branch Piping Length 5m
Level difference : 0m
2. TC : Total Capacity (kW)
PI : Power Input (kW)
-15.0 6.49
2.10
6.49
2.15
6.48
2.20
6.48
2.22
6.48
2.25
6.48
2.31
-13.0 6.68
2.13
6.68
2.17
6.67
2.22
6.78
2.25
6.78
2.27
6.78
2.32
-11.0 6.87
2.16
6.87
2.20
6.87
2.24
6.95
2.26
6.95
2.28
6.96
2.33
-10.0 6.97
2.17
6.97
2.21
6.96
2.25
7.04
2.27
7.04
2.29
7.04
2.34
-9.1 7.06
2.19
7.05
2.22
7.05
2.25
7.12
2.28
7.12
2.30
7.12
2.34
-7.6 7.20
2.21
7.20
2.24
7.19
2.27
7.25
2.29
7.25
2.31
7.26
2.35
-5.6 7.39
2.24
7.39
2.26
7.39
2.29
7.43
2.31
7.43
2.32
7.43
2.35
-3.7 7.57
2.26
7.57
2.28
7.57
2.31
7.60
2.32
7.60
2.33
7.60
2.36
-0.7 7.86
2.31
7.86
2.32
7.86
2.34
7.86
2.35
7.86
2.35
7.86
2.37
0.0 7.93
2.32
7.92
2.33
7.92
2.34
7.92
2.35
7.92
2.36
7.92
2.38
1.0 8.02
2.33
8.02
2.34
8.02
2.35
8.01
2.36
8.01
2.37
8.01
2.38
2.2 8.14
2.35
8.14
2.36
8.13
2.36
8.12
2.37
8.12
2.37
8.12
2.38
4.1 8.32
2.37
8.32
2.38
8.32
2.38
8.28
2.38
8.28
2.39
8.28
2.39
6.0 8.58
2.28
8.54
2.34
8.50
2.40
8.45
2.40
8.45
2.40
8.45
2.40
7.9 8.92
2.32
8.88
2.39
8.85
2.45
8.84
2.49
8.83
2.53
8.83
2.61
9.8 9.28
2.37
9.25
2.44
9.23
2.51
9.22
2.55
9.22
2.59
9.21
2.67
11.8 9.69
2.43
9.67
2.51
9.65
2.58
9.65
2.62
9.65
2.66
9.64
2.75
13.7 10.11
2.50
10.09
2.57
10.08
2.65
10.07
2.69
10.06
2.73
10.03
2.82
15.0 10.41
2.54
10.39
2.62
10.37
2.69
10.35
2.73
10.33
2.77
10.28
2.86
18.0 11.08
2.60
11.03
2.68
10.95
2.75
10.89
2.79
10.83
2.82
10.65
2.88
-15.0 5.20
1.51
5.20
1.55
5.20
1.59
5.20
1.60
5.20
1.62
5.21
1.67
-13.0 5.35
1.53
5.35
1.57
5.35
1.60
5.43
1.62
5.44
1.64
5.44
1.68
-11.0 5.50
1.55
5.50
1.58
5.50
1.61
5.57
1.63
5.57
1.65
5.58
1.68
-10.0 5.58
1.56
5.58
1.59
5.58
1.62
5.64
1.64
5.64
1.65
5.65
1.69
-9.1 5.65
1.57
5.65
1.60
5.65
1.63
5.71
1.64
5.71
1.66
5.71
1.69
-7.6 5.76
1.59
5.76
1.61
5.76
1.64
5.81
1.65
5.81
1.66
5.82
1.69
-5.6 5.91
1.61
5.92
1.63
5.92
1.65
5.95
1.66
5.95
1.67
5.95
1.70
-3.7 6.06
1.63
6.06
1.65
6.06
1.66
6.08
1.67
6.08
1.68
6.09
1.70
-0.7 6.29
1.66
6.29
1.67
6.29
1.68
6.29
1.69
6.29
1.70
6.30
1.71
0.0 6.34
1.67
6.34
1.68
6.34
1.69
6.34
1.69
6.34
1.70
6.34
1.71
1.0 6.42
1.68
6.42
1.69
6.42
1.69
6.41
1.70
6.41
1.70
6.41
1.71
2.2 6.51
1.69
6.51
1.70
6.51
1.70
6.50
1.70
6.50
1.71
6.50
1.72
4.1 6.65
1.71
6.66
1.71
6.66
1.72
6.63
1.71
6.63
1.72
6.63
1.72
6.0 6.88
1.64
6.84
1.69
6.80
1.73
6.76
1.73
6.76
1.73
6.76
1.73
7.9 7.15
1.67
7.10
1.72
7.07
1.76
7.05
1.78
7.04
1.81
7.02
1.86
9.8 7.42
1.71
7.39
1.75
7.36
1.80
7.34
1.82
7.33
1.85
7.32
1.90
11.8 7.74
1.75
7.71
1.80
7.68
1.84
7.66
1.87
7.65
1.90
7.63
1.95
13.7 8.06
1.79
8.02
1.84
7.99
1.89
7.98
1.91
7.96
1.94
7.93
2.00
15.0 8.28
1.81
8.25
1.86
8.21
1.91
8.19
1.94
8.16
1.97
8.11
2.02
18.0 8.78
1.85
8.72
1.90
8.63
1.95
8.58
1.97
8.53
1.99
8.38
2.03
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
Combination
Capacity Index
(kBtu/h(%))
Outdoor Air
Temperature
(°CWB)
16.0
18.0
20.0
21.0
22.0
24.0
Indoor Air Temperature (°CDB)
24
(50%)
19
(40%)