2. Distributor type MULTI F DX (1 phase)
Part 2 Product data_Outdoor units
[Heating capacity]
23 15,456 4.5 27,948 8.2 32,138 9.4 1,490 2,267 3,240
24 16,023 4.7 28,973 8.5 33,407 9.8 1,579 2,402 3,433
25 16,590 4.9 29,998 8.8 34,676 10.2 1,626 2,473 3,535
26 17,157 5.0 31,024 9.1 35,945 10.5 1,672 2,544 3,637
27 17,724 5.2 32,049 9.4 37,214 10.9 1,719 2,616 3,739
28 18,290 5.4 33,074 9.7 38,483 11.3 1,766 2,687 3,842
29 18,857 5.5 34,099 10.0 39,752 11.7 1,813 2,759 3,944
30 19,424 5.7 35,124 10.3 41,021 12.0 1,860 2,830 4,046
31 19,991 5.9 36,149 10.6 42,290 12.4 1,907 2,902 4,148
32 20,558 6.0 37,174 10.9 43,560 12.8 1,954 2,973 4,250
33 21,125 6.2 38,199 11.2 44,648 13.1 1,973 3,001 4,290
34 21,692 6.4 39,224 11.5 45,736 13.4 1,991 3,029 4,330
35 22,259 6.5 40,249 11.8 46,824 13.7 2,009 3,057 4,370
36 22,825 6.7 41,274 12.1 47,912 14.0 2,028 3,085 4,409
37 23,392 6.9 42,299 12.4 49,000 14.4 2,046 3,112 4,449
38 23,959 7.0 43,324 12.7 50,286 14.7 2,064 3,140 4,489
39 24,526 7.2 44,349 13.0 51,572 15.1 2,082 3,168 4,529
40 25,093 7.4 45,374 13.3 52,858 15.5 2,101 3,196 4,569
41 25,660 7.5 46,399 13.6 54,144 15.9 2,119 3,224 4,609
42 26,227 7.7 47,425 13.9 55,430 16.2 2,137 3,252 4,648
43 26,794 7.9 48,450 14.2 56,716 16.6 2,156 3,280 4,688
44 27,360 8.0 49,475 14.5 58,000 17.0 2,174 3,308 4,728
45 27,927 8.2 50,500 14.8 58,292 17.1 2,211 3,365 4,812
46 28,494 8.4 51,525 15.1 58,584 17.2 2,246 3,417 4,884
47 29,061 8.5 52,550 15.4 58,876 17.3 2,299 3,498 5,000
48 29,628 8.7 53,575 15.7 59,168 17.3 2,352 3,579 5,116
49 30,195 8.8 54,600 16.0 59,460 17.4 2,406 3,660 5,232
50 30,762 9.0 54,943 16.1 59,750 17.5 2,459 3,741 5,348
51 31,329 9.2 55,286 16.2 60,375 17.7 2,512 3,822 5,464
52 31,896 9.3 55,629 16.3 61,000 17.9 2,566 3,903 5,580
53 32,462 9.5 55,971 16.4 61,176 17.9 2,579 3,924 5,609
54 33,029 9.7 56,314 16.5 61,353 18.0 2,593 3,944 5,638
55 33,596 9.8 56,657 16.6 61,529 18.0 2,606 3,964 5,667
56 34,163 10.0 57,000 16.7 61,706 18.1 2,619 3,985 5,696
57 34,730 10.2 57,343 16.8 61,882 18.1 2,633 4,005 5,725
58 35,297 10.3 57,686 16.9 62,059 18.2 2,646 4,025 5,754
59 35,864 10.5 58,029 17.0 62,235 18.2 2,659 4,046 5,783
60 36,431 10.7 58,371 17.1 62,412 18.3 2,673 4,066 5,812
61 36,997 10.8 58,714 17.2 62,588 18.3 2,686 4,086 5,841
62 37,564 11.0 59,057 17.3 62,765 18.4 2,699 4,107 5,870
63 38,131 11.2 59,400 17.4 62,941 18.4 2,734 4,160 5,900
64 38,698 11.3 59,636 17.5 63,047 18.5 2,726 4,147 5,929
65 39,265 11.5 59,872 17.5 63,153 18.5 2,739 4,168 5,958
66 39,832 11.7 60,108 17.6 63,259 18.5 2,753 4,188 5,987
67 40,399 11.8 60,344 17.7 63,365 18.6 2,766 4,208 6,016
68 40,966 12.0 60,580 17.8 63,471 18.6 2,780 4,229 6,045
69 41,532 12.2 60,816 17.8 63,576 18.6 2,793 4,249 6,074
70 42,099 12.3 61,052 17.9 63,682 18.7 2,806 4,269 6,103
71 42,666 12.5 61,288 18.0 63,788 18.7 2,820 4,290 6,132
72 43,233 12.7 61,524 18.0 63,894 18.7 2,833 4,310 6,161
73 43,800 12.8 61,760 18.1 64,000 18.8 2,846 4,330 6,190
Total indoor unit
capacity
(kBtu/h)
Min
Heating capacity
Rated
Max
Btu/h
kW
Btu/h
kW
Btu/h
kW
Min
Rated
Max
Input (W)
Note :
1. Cooling Capacity is based on : indoor temp.27°C DB, 19°C WB
; outdoor temp. 35°C DB, 24°C WB
2. Heating Capacity is based on : indoor temp.20°C DB, 15°C WB
; outdoor temp. 7°C DB, 6°C WB
3. The rated capacities above show the rise in the total indoor unit capacity when operating frequency is
constant.
Values for changes in capacity are fixed after accounting for variations in operating frequency and should
be used as reference values.
4. Total capacity index of indoor unit should be within 23~73 Btu/h(40%~130%)
5. At least two indoor units should be connected.