3. Distributor type MULTI F DX (3 phase)
33
_
Heat pump 50Hz/R410A
Part 2 Product data_Outdoor units
2) Rate of change in capacity due to the branch piping length
5 / 7k Btu/h 2.1 kW models
9k Btu/h 2.6 kW models
Piping
Length
5
100.0
100.0
10
98.0
99.5
15
96.0
98.9
Rate of Change in Capacity
Cooling(%)
Heating(%)
Piping
Length
5
100.0
100.0
10
97.0
98.3
15
94.0
96.5
Rate of Change in Capacity
Cooling(%)
Heating(%)
Piping
Length
5
100.0
100.0
10
97.8
99.2
15
95.5
98.4
Rate of Change in Capacity
Cooling(%)
Heating(%)
Piping
Length
5
100.0
100.0
10
97.8
99.5
15
95.5
99.0
Rate of Change in Capacity
Cooling(%)
Heating(%)
Piping
Length
5
100.0
100.0
10
97.5
99.5
15
95.0
98.9
Rate of Change in Capacity
Cooling(%)
Heating(%)
12k Btu/h 3.5 kW models
18k Btu/h 5.3 kW models
24k Btu/h 7.0 kW models