Heat Pump
50Hz/R410A
_
101
1. Multiple piping type MULTI F
Part 2 Product data_Outdoor units
TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW
Combination
capacity index
(kBtu/h)
Outdoor
air temp.:
(°CDB)
Operation
14 16
18 19 22 24
Indoor air temp.: (°CWB)
7+7+9+18
4 Units
Notes:
1. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5m
Level difference : 0m
2. TC : Total Capacity (kW)
PI : Power Input (kW)
22 7.53 1.08 8.00 1.45 8.47 1.57 8.70 1.59 9.41 1.61 9.88 1.61
25 7.35 1.14 7.82 1.50 8.29 1.61 8.52 1.64 9.23 1.66 9.70 1.68
32 6.93 1.53 7.40 1.81 7.87 1.90 8.11 1.92 8.82 1.97 9.29 2.00
35 6.76 1.71 7.23 1.94 7.70 2.01 7.91 1.98 8.64 2.08 9.11 2.12
40 6.46 1.88 6.93 2.03 7.40 2.05 7.64 2.06 8.34 2.09 8.81 2.14
43 6.28 1.84 6.75 1.93 7.22 1.92 7.46 1.92 8.16 1.94 8.64 1.98
46 6.10 1.65 6.58 1.67 7.05 1.63 7.28 1.62 7.99 1.62 8.46 1.66