84/102
17200234_002_C1/2016 - © Leybold
602494EA.DOCX
•
Gain Kp
Select a gain setting between 0.1 and 100.0.
Command
Response
Entry
RSP=xxx.x
RSP=xxx.x
Example
RSP=020.0
RSP=_20.0
Inquiry
RSP?
RSP=xxx.x
Example
RSP?
RSP=_20.0
Table 5-22
•
Reset time Tn
Select a reset time between 0.0 and 3600.0 s.
Command
Response
Entry
RSI=xxxx.x
RSI=xxxx.x
Example
RSI=0030.3
RSI=_ _30.3
Inquiry
RSI?
RSI=xxxx.x
Example
RSI?
RSI=_ _30.3
Table 5-23
•
Derivative time Tv
Select a derivative time between 0.0 and 3600.0 s.
Command
Response
Entry
RSD=xxxx.x
RSD=xxxx.x
Example
RSD=0021.2
RSD=_ _21.2
Inquiry
RSD?
RSD=xxxx.x
Example
RSD?
RSD=_ _21.2
Table 5-24