Troubleshooting and fault elimination
Fault messages
l
83
LDEDS−CCU210B EN 4.0
Display
1
Fault
Cause
Remedy
F001
H001
Motor: overcurrent
Motor overloaded by impermissible
continuous current
Check drive dimensioning.
Rated motor current set incorrectly
Check setting of C0120.
F002
Control system: internal temperature
too high
Ambient temperature too high
Reduce ambient temperature.
F003
H003
Control system: mains voltage too
low
Failure of one or several mains phases
l
Check supply feeder/collector.
l
Check fuses.
Mains voltage too low
Check mains voltage.
F004
Control system: mains voltage too
high
Mains voltage too high
l
Check supply feeder/collector.
l
Check mains voltage.
l
Check setting of C0016.
F005
Control system: fault in the output
stage
Fault in wiring on the motor side
Correct motor wiring.
Motor defective
Replace motor.
Control system defective
Replace control system.
F006
H006
Motor: high−resistance thermistor
Motor too warm from impermissibly
high currents
Check drive dimensioning.
No PTC or thermal contact connected
Connect PTC or thermal contact or
switch off monitoring with C0120 = 0.
F008
Frequency inverter: parameter error
Inconsistency within the parameters
of the frequency inverter, e. g.
because the external data memory
has been removed during a voltage
was applied
l
Load Lenze setting
l
Transfer parameter data again.
Thereby always wait until the
PAr
message goes out. Only then
switch off the voltage.
F011
H011
Motor: phase U failed
Motor phase U failed
Check motor and motor wiring.
F012
H012
Motor: phase V failed
Motor phase V failed
Check motor and motor wiring.
F013
H013
Motor: phase W failed
Motor phase W failed
Check motor and motor wiring.
F014
Frequency inverter: overload of
internal brake resistor
Overload by operation in generator
mode
l
Let control system cool down.
l
Reduce number of brake
applications.
l
Reduce loading of vehicle.
F018
Frequency inverter: initialisation error Internal communication error
Switch off mains voltage and then
switch it on again. If the error occurs
again, replace control system
F019
Frequency inverter: not ready for
operation
Internal communication error
Switch off mains voltage and then
switch it on again. If the error occurs
again, replace control system.
H020
Control: 24 V voltage supply too low
l
Failure of one or several mains
phases
l
Mains voltage too low
l
Overload of the 24 V voltage
supply on the control connections
for encoders, sensors, etc.
l
Check supply feeder/collector
l
Check fuses
l
Check mains voltage
l
Check encoders, sensors connected
and their cabling