5.3.9
Heatsink Temperature Monitoring
Parameter
Name / value range / [default setting]
Info
0x2D84:001
(PAR 117/001)
Heatsink temperature monitoring: Actual value
(Heatsink temp.: Heatsink temp.)
•
Read only: x.x °C
Display of the current heatsink temperature.
0x2D84:002
Heatsink temperature monitoring: Warning threshold
50.0 ... [80.0]* ... 100.0 °C
•
Default setting depending on the size.
Warning threshold for temperature monitoring.
•
If the heatsink temperature exceeds the threshold set here, the inver-
ter outputs a warning.
•
The warning is reset with a hysteresis of approx. 5 °C.
•
If the heatsink temperature increases further and exceeds the non-
adjustable error threshold (100 °C), ), the inverter changes to the
"Fault" device status. Further operation of the inverter is disabled by
controller inhibit.
5.3.10
Diagnostics timer
The following parameters provide some information about the use of the inverter.
This includes the following information:
•
Operating and power-on time of the inverter/control unit
•
Operating time of the internal fan
•
Number of switching cycles of the mains voltage
•
Number of switching cycles of the relay
•
Number of short-circuits and earth faults that have occurred
•
Display of the number of "Clamp responds too often" errors that have occurred.
Parameter
Name / value range / [default setting]
Info
0x2D81:001
(PAR 151/001)
Service life timer: Operating time
(Timer/counter: Operating time)
•
Read only: x s
Display showing for how long the inverter has been running so far "Oper-
ation enabled" device state).
0x2D81:002
(PAR 151/002)
Display showing for how long the inverter has been switched on so far.
0x2D81:003
(PAR 151/003)
Service life timer: Control unit operating time
(Timer/counter: CU oper. time)
•
Read only: x ns
Display showing how long the control unit of the inverter has been
switched on for so far.
•
This also includes the time within which the control unit has only
been supplied with an external 24 V voltage.
0x2D81:004
(PAR 151/004)
Service life timer: Main Switching Cycles
(Timer/counter: Power cycles)
•
Read only
Display of the number of switching cycles of the mains voltage.
0x2D81:005
(PAR 151/005)
Service life timer: Relay switching cycles
(Timer/counter: Relay cycles)
•
Read only
Display of the number of switching cycles of the relay.
0x2D81:006
(PAR 151/006)
Service life timer: Short-circuit counter
(Timer/counter: Short-circ. counter)
•
Read only
Display of the number of short circuits that have occurred.
0x2D81:007
(PAR 151/007)
Service life timer: Earth fault counter
(Timer/counter: Earth fault counter)
•
Read only
Display of the number of earth faults that have occurred.
0x2D81:008
(PAR 151/008)
Service life timer: Clamp active
(Timer/counter: Clamp active)
•
Read only
Display of the number of "Clamp responds too often" errors that have
occurred.
•
"Clamp" = short-time inhibit of the inverter in V/f operation when the
current limit shown in
0x2DDF:002
is reached.
0x2D81:009
(PAR 151/009)
Service life timer: Fan operating time
(Timer/counter: Fan oper. time)
•
Read only: x s
Display showing for how long the internal fan has been running so far.
Diagnostics and fault elimination
Diagnostics
Heatsink Temperature Monitoring