Address
Name / Subindex: Name
Default setting
Setting range
D / F / A / M
012
: Preset value 12
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
013
: Preset value 13
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
014
: Preset value 14
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
015
: Preset value 15
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
0x2912
Preset torque values
001
: Preset value 1
100.0 %
-400.0 ... 400.0 %
I16 / 10 / P / -
002
: Preset value 2
100.0 %
-400.0 ... 400.0 %
I16 / 10 / P / -
003
: Preset value 3
100.0 %
-400.0 ... 400.0 %
I16 / 10 / P / -
004
: Preset value 4
100.0 %
-400.0 ... 400.0 %
I16 / 10 / P / -
005
: Preset value 5
100.0 %
-400.0 ... 400.0 %
I16 / 10 / P / -
006
: Preset value 6
100.0 %
-400.0 ... 400.0 %
I16 / 10 / P / -
007
: Preset value 7
100.0 %
-400.0 ... 400.0 %
I16 / 10 / P / -
008
: Preset value 8
100.0 %
-400.0 ... 400.0 %
I16 / 10 / P / -
0x2915
Minimum frequency
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
0x2916
Maximum frequency
50.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
0x2917
Acceleration time 1
5.0 s
0.0 ... 3600.0 s
U16 / 10 / P / r
0x2918
Deceleration time 1
5.0 s
0.0 ... 3600.0 s
U16 / 10 / P / r
0x2919
Acceleration time 2
5.0 s
0.0 ... 3600.0 s
U16 / 10 / P / -
0x291A
Deceleration time 2
5.0 s
0.0 ... 3600.0 s
U16 / 10 / P / -
0x291B
Auto-changeover threshold of ramp 2
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
0x291C
Quick stop deceleration time
1.0 s
0.0 ... 3600.0 s
U16 / 10 / P / -
0x291E
S-Ramp characteristic
001
: Smoothing factor
0.0 %
0.0 ... 100.0 %
U16 / 10 / P / -
0x291F
Skip frequencies
001
: Frequency 1
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
002
: Bandwidth 1
0.0 Hz
0.0 ... 10.0 Hz
U8 / 10 / P / -
003
: Frequency 2
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
004
: Bandwidth 2
0.0 Hz
0.0 ... 10.0 Hz
U8 / 10 / P / -
005
: Frequency 3
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
006
: Bandwidth 3
0.0 Hz
0.0 ... 10.0 Hz
U8 / 10 / P / -
016
: Status
-
- (Read only)
U16 / 1 / X / -
032
: Input frequency
x.xx Hz
- (Read only)
I32 / 100 / X / -
033
: Output frequency
x.xx Hz
- (Read only)
I32 / 100 / X / -
0x2939
Switching frequency
8 kHz variable / drive-
optimised / 4 kHz min.
[21]
Selection list
U8 / 1 / PC / -
0x2942
Current controller parameters
001
: Gain
42.55 V/A *
0.00 ... 750.00 V/A
U32 / 100 / P / -
002
: Reset time
4.50 ms *
0.01 ... 2000.00 ms
U32 / 100 / P / -
0x2947
Inverter characteristic
001
: y1 = U1 (x = 0.00 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
002
: y2 = U2 (x = 6.25 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
003
: y3 = U3 (x = 12.50 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
004
: y4 = U4 (x = 18.75 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
005
: y5 = U5 (x = 25.00 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
006
: y6 = U6 (x = 31.25 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
007
: y7 = U7 (x = 37.50 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
008
: y8 = U8 (x = 42.75 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
009
: y9 = U9 (x = 50.00 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
010
: y10 = U10 (x = 56.25 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
011
: y11 = U11 (x = 62.50 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
012
: y12 = U12 (x = 68.75 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
013
: y13 = U13 (x = 75.00 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
014
: y14 = U14 (x = 81.25 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
* Default setting depending on the size.
Firmware-Version 01.01.01.00
Appendix
Parameter attribute list
241