Address
Name / Subindex: Name
Default setting
Setting range
D / F / A / M
0x2832
Motor identification status
-
- (Read only)
U16 / 1 / O / -
0x2833
Lenze status word 2
-
- (Read only)
U16 / 1 / O / t
0x2838
Start/stop configuration
001
: Start method
Normal [0]
Selection list
U8 / 1 / CP / -
002
: Start at switch-on
Off [0]
Selection list
U8 / 1 / P / -
003
: Stop method
Standard Ramp [1]
Selection list
U8 / 1 / P / -
0x2839
Fault configuration
002
: Restart delay
3.0 s
0.0 ... 1000.0 s
U16 / 10 / P / -
003
: Number of restart attempts
5
0 ... 255
U8 / 1 / P / -
004
: Down-counting time of glitch counter
5.0 s
0.1 ... 3600.0 s
U16 / 10 / P / -
005
: Current counter content of glitch counter
-
- (Read only)
U8 / 1 / - / -
0x283A
Limitation of rotation
Forwards and backwards
[1]
Selection list
U8 / 1 / P / -
0x2857
CANopen monitoring
001
: RPDO1-Timeout
Error [3]
Selection list
U8 / 1 / P / -
002
: RPDO2-Timeout
Error [3]
Selection list
U8 / 1 / P / -
003
: RPDO3-Timeout
Error [3]
Selection list
U8 / 1 / P / -
005
: Heartbeat-Timeout Consumer 1
Error [3]
Selection list
U8 / 1 / P / -
006
: Heartbeat-Timeout Consumer 2
Error [3]
Selection list
U8 / 1 / P / -
007
: Heartbeat-Timeout Consumer 3
Error [3]
Selection list
U8 / 1 / P / -
008
: Heartbeat-Timeout Consumer 4
Error [3]
Selection list
U8 / 1 / P / -
010
: "Bus-off" state change
Trouble [2]
Selection list
U8 / 1 / P / -
011
: Warning
Warning [1]
Selection list
U8 / 1 / P / -
0x2858
Modbus monitoring
001
: Response to time-out
Error [3]
Selection list
U8 / 1 / P / -
002
: Time-out
2.0 s
0.0 ... 300.0 s
U16 / 10 / P / -
0x2860
Standard setpoint sources
001
: Frequency setpoint source
Analog input 1 [2]
Selection list
U8 / 1 / P / -
002
: Process controller setpoint source
Keypad [1]
Selection list
U8 / 1 / P / -
003
: Torque setpoint source
Analog input 1 [2]
Selection list
U8 / 1 / P / -
0x2862
Keypad setpoint increment
1
1 ... 100
U16 / 1 / P / -
0x2863
Keypad language selection
English [1]
Selection list
U8 / 1 / P / -
0x2864
Keypad status display
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
0x2900
Speed controller parameters
001
: Gain
0.00193 Nm/rpm *
0.00000 ...
20000.00000 Nm/rpm
U32 / 100000 / P / -
002
: Reset time
80.0 ms *
1.0 ... 6000.0 ms
U16 / 10 / P / -
0x2904
Filter time
2.0 ms
0.0 ... 50.0 ms
U16 / 10 / P / -
0x2910
Moment of inertia values
001
: Motor
3.70 kg cm² *
0.00 ... 20000000.00 kg cm²
U32 / 100 / P / -
002
: Load
3.70 kg cm² *
0.00 ... 20000000.00 kg cm²
U32 / 100 / P / -
003
: Coupling
With clearance [2]
Selection list
U8 / 1 / P / -
0x2911
Preset frequency values
001
: Preset value 1
20.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
002
: Preset value 2
40.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
003
: Preset value 3
50.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
004
: Preset value 4
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
005
: Preset value 5
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
006
: Preset value 6
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
007
: Preset value 7
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
008
: Preset value 8
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
009
: Preset value 9
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
010
: Preset value 10
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
011
: Preset value 11
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
* Default setting depending on the size.
Firmware-Version 01.01.01.00
Appendix
Parameter attribute list
240
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: [email protected]