Parameter
Name / value range / [default setting]
Info
0x400E:003
(PAR 505/003)
NETWordIN1 function assignment: Bit 2
(NETWordIN1 config.: NETWordIN1.02)
•
Setting can only be changed if controller inhibit is
active.
•
For possible settings see description for
0x400E:
001 (PAR 505/001)
.
^
98
Definition of the function that is to be triggered via bit 2 of the mappa-
ble NETWordIN1 data word.
03 Quick stop
Trigger bit = 1: "Quick stop" function activated.
Trigger bit = 0: no action / deactivate function again.
Notes:
•
The "Quick stop" function brings the motor to a standstill within the
deceleration time set in
0x291C (PAR 225)
.
•
The "Quick stop" function has a higher priority than the "Start enable"
function.
0x400E:004
(PAR 505/004)
NETWordIN1 function assignment: Bit 3
(NETWordIN1 config.: NETWordIN1.03)
•
Setting can only be changed if controller inhibit is
active.
•
For possible settings see description for
0x400E:
001 (PAR 505/001)
.
^
98
Definition of the function that is to be triggered via bit 3 of the mappa-
ble NETWordIN1 data word.
8 Forward run (CW)
Trigger bit = 0-1 edge: drive is started in forward rotating direction (CW).
Trigger bit = 1-0 edge: drive is stopped again.
Notes:
•
In order to start the drive with this function, the "Stop [2]" function
has to be assigned to a bit in order to provide a stop command.
•
The stop method can be selected in
0x2838:003 (PAR 203/003)
.
•
In the case of a bipolar setpoint selection (e.g
±
10 V), the function is
executed irrespective of the rotating direction. The rotating direction
is determined by the sign of the setpoint.
•
The function also serves to realise an automatic start after switch-on.
4
Starting performance
^
72
•
The "Reversal [13]" function can be used in connection with this func-
tion.
0x400E:005
(PAR 505/005)
NETWordIN1 function assignment: Bit 4
(NETWordIN1 config.: NETWordIN1.04)
•
Setting can only be changed if controller inhibit is
active.
•
For possible settings see description for
0x400E:
001 (PAR 505/001)
.
^
98
Definition of the function that is to be triggered via bit 4 of the mappa-
ble NETWordIN1 data word.
13 Reversal
Trigger bit = 1: the setpoint specified is inverted (i. e. the sign is inver-
ted).
Trigger bit = 0: no action / deactivate function again.
0x400E:006
(PAR 505/006)
NETWordIN1 function assignment: Bit 5
(NETWordIN1 config.: NETWordIN1.05)
•
Setting can only be changed if controller inhibit is
active.
•
For possible settings see description for
0x400E:
001 (PAR 505/001)
.
^
98
Definition of the function that is to be triggered via bit 5 of the mappa-
ble NETWordIN1 data word.
05 DC braking
Trigger bit = 1: "DC braking" function activated.
Trigger bit = 0: no action / deactivate function again.
0x400E:007
(PAR 505/007)
NETWordIN1 function assignment: Bit 6
(NETWordIN1 config.: NETWordIN1.06)
•
Setting can only be changed if controller inhibit is
active.
•
For possible settings see description for
0x400E:
001 (PAR 505/001)
.
^
98
Definition of the function that is to be triggered via bit 6 of the mappa-
ble NETWordIN1 data word.
00 Not active
Trigger bit without any function.
Configuring the network
General network settings