Address
Name / Subindex: Name
Default setting
Setting range
D / F / A / M
015
: y15 = U15 (x = 87.50 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
016
: y16 = U16 (x = 93.25 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
017
: y17 = U17 (x = 100.00 %)
0.00 V *
0.00 ... 20.00 V
U16 / 100 / P / -
0x29C0
Field controller settings
001
: Gain
59.68 A/Vs *
0.00 ... 50000.00 A/Vs
U32 / 100 / P / -
002
: Reset time
45.5 ms *
1.0 ... 6000.0 ms
U16 / 10 / P / -
0x29E0
Field weakening controller settings
001
: Gain
0.000 Vs/V *
0.000 ... 2000000.000 Vs/V
U32 / 1000 / P / -
002
: Reset time
1478.3 ms *
1.0 ... 240000.0 ms
U32 / 10 / P / -
0x2B00
V/f characteristic shape
Linear [0]
Selection list
U8 / 1 / CP / -
0x2B01
V/f characteristic data
001
: Base voltage
230 V *
0 ... 5000 V
U16 / 1 / P / -
002
: Base frequency
50 Hz *
0 ... 599 Hz
U16 / 1 / P / -
0x2B08
V/f Imax controller
001
: Gain
0.284 Hz/A *
0.000 ... 1000.000 Hz/A
U32 / 1000 / P / -
002
: Reset time
2.3 ms *
1.0 ... 2000.0 ms
U32 / 10 / P / -
0x2B09
Slip compensation
001
: Gain
100.00 %
-200.00 ... 200.00 %
I16 / 100 / P / -
002
: Filter time
5 ms
1 ... 6000 ms
U16 / 1 / P / -
0x2B0A
Oscillation damping
001
: Gain
20 %
-100 ... 100 %
I16 / 1 / P / -
002
: Filter time
5 ms
1 ... 600 ms
U16 / 1 / P / -
0x2B0C
Override point of field weakening
0.0 Hz
-599.0 ... 599.0 Hz
I16 / 10 / P / -
0x2B0E
Frequency setpoint
x.x Hz
- (Read only)
I16 / 10 / O / t
0x2B0F
V/f operation: actual frequency of motor shaft
x.x Hz
- (Read only)
I16 / 10 / O / t
0x2B12
V/f voltage boost
001
: Fixed boost
2.5 % *
0.0 ... 20.0 %
U8 / 10 / P / -
002
: Boost at acceleration
0.0 %
0.0 ... 20.0 %
U8 / 10 / P / -
0x2B40
SLVC
001
: Gain
0.2686 Hz/A *
0.0000 ... 1000.0000 Hz/A
U32 / 10000 / P / -
002
: Reset time
2.3 ms *
1.0 ... 2000.0 ms
U32 / 10 / P / -
0x2B84
DC braking
001
: Current
0.0 %
0.0 ... 200.0 %
U16 / 10 / P / -
002
: Automatic hold time
0.0 s
0.0 ... 999.9 s
U16 / 10 / P / -
003
: Automatic operating threshold
0.0 Hz
0.0 ... 599.0 Hz
U16 / 10 / P / -
0x2BA1
Flying restart circuit
001
: Current
30 %
0 ... 100 %
U16 / 1 / P / -
002
: Start frequency
20.0 Hz
-599.0 ... 599.0 Hz
I16 / 10 / P / -
003
: Restart time
5911 ms *
1 ... 60000 ms
U16 / 1 / P / -
008
: Flying restart frequency
x.x Hz
- (Read only)
I16 / 10 / O / t
0x2C00
Motor control type
V/f characteristic control
(VFC open loop) [6]
Selection list
U8 / 1 / CP / -
0x2C01
Motor parameters
001
: Number of pole pairs
-
- (Read only)
U8 / 1 / - / -
002
: Stator resistance
10.1565 Ohm *
0.0000 ... 125.0000 Ohm
U32 / 10000 / P / -
003
: Stator leakage inductance
23.566 mH *
0.000 ... 500.000 mH
U32 / 1000 / P / -
004
: Rated speed
1450 rpm
50 ... 50000 rpm
U16 / 1 / P / -
005
: Rated frequency
50.0 Hz
1.0 ... 1000.0 Hz
U16 / 10 / P / -
006
: Rated power
0.25 kW *
0.00 ... 655.35 kW
U16 / 100 / P / -
007
: Rated voltage
230 V *
0 ... 65535 V
U16 / 1 / P / -
008
: Cosine phi
0.80
0.00 ... 1.00
U16 / 100 / P / -
010
: Name
Text
STRING[25] / 1 / P / -
* Default setting depending on the size.
Firmware-Version 01.01.01.00
Appendix
Parameter attribute list
242