11.13.2
Analog input 2
Settings for analog input 2.
Details
•
The internal output signal of the analog input is either a frequency setpoint or a process
controller setpoint that is calculated from the percentage input value.
•
The setting range can be individually defined for speed mode and process controller mode.
•
Optionally, a dead band can be configured. Setpoints in this range that are centred around
0 Hz are ignored which is used to eliminate smallest signal levels for the setpoint frequency
0 Hz.
Definition of the setting range and dead band for speed mode
0
❹
100
-100
❶
❷
❸
❹
[Hz]
[%]
Parameter
Name
Notes
❶
0x2637:003
(PAR 431/003)
Max value [Hz]
❷
0x2637:002
(PAR 431/002)
Min value [Hz]
For all modes except -10 V ... +10 V
❸
Only for mode -10 V ... +10 V
❹
0x2637:007
(PAR 431/007)
Dead band
A setting > 0 produces a dead band to the zero
crossing of the [Hz] axis. The value set defines
half the width of the dead band in [%].
Parameter
Name / value range / [default setting]
Info
0x2637:001
(PAR 431/001)
Analog input 2: Input range
(Analog input 2: AI2 config.)
Definition of the input range.
0 0 … 10 VDC
1 0 … 5 VDC
2 2 … 10 VDC
3 -10 … +10 VDC
4 4 … 20 mA
5 0 … 20 mA
0x2637:002
(PAR 431/002)
Analog input 2: Min value [Hz]
(Analog input 2: AI2 freq @ min)
-1000.0 ... [0.0] ... 1000.0 Hz
Definition of the setting range for speed mode.
•
A negative setting only shifts the offset, but does not change the
rotating direction.
•
The rotating direction is reversed if Min value [Hz] > Max value [Hz] is
set.
0x2637:003
(PAR 431/003)
Analog input 2: Max value [Hz]
(Analog input 2: AI2 freq @ max)
-1000.0 ... [50.0] ... 1000.0 Hz
0x2637:004
(PAR 431/004)
Analog input 2: Min value [Punit/%]
(Analog input 2: AI2 PID/Mom@min)
-300.00 ... [0.00] ... 300.00 PUnit/%
Definition of the setting range for process controller mode and torque
mode.
0x2637:005
(PAR 431/005)
Analog input 2: Max value [Punit/%]
(Analog input 2: AI2 PID/Mom@max)
-300.00 ... [100.00] ... 300.00 PUnit/%
Flexible I/O configuration
Configuration of analog inputs
Analog input 2
213