8400 StateLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
ot1: Maximum torque reached [xx.0123.00001]
oC7: Motor overcurrent [xx.0123.00007]
oU: DC bus overvoltage [xx.0123.00014]
LU: DC bus undervoltage [xx.0123.00015]
Response
(Lenze setting printed in bold)
Setting:
C00608
(
;
Adjustable response)
:
0: No Reaction
;
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
;
5: Warning
6: Information
Cause
Remedy
The device indicates that the maximally possible torque
at the motor shaft has been reached.
•
C00057
displays the current torque.
Reduce motor load.
Response
(Lenze setting printed in bold)
0: No Reaction
:
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
The maximum current monitoring has tripped.
• The instantaneous value of the motor current has
exceeded the limit value set in
C00939
.
Check and, if required, correct dimensioning of the load
with regard to the installed device power.
Response
(Lenze setting printed in bold)
0: No Reaction
;
1: Fault
:
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
The device has detected an overvoltage in the DC bus. To
protect the device hardware, the inverter control is
switched off.
• Depending on the configuration of the auto-start lock
function,
C00142
serves to set that, if this error has
been tripped, the controller only starts after the
controller inhibit is switched.
• If this error message remains active longer than the
time set in
C00601
, a "Fault" is tripped.
• Reduce load in generator mode.
• Use a brake resistor.
• Use a regenerative power supply unit.
• Establish a DC-bus connection.
Response
(Lenze setting printed in bold)
Setting:
C00600/1
(
;
Adjustable response)
0: No Reaction
;
1: Fault
:
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
The device has detected a DC bus undervoltage. The
inverter control is switched off because the drive
properties of the motor control cannot be provided
anymore due to the DC bus undervoltage.
• Depending on the configuration of the auto-start lock
function,
C00142
serves to set that, if this error has
been tripped, the controller only starts after the
controller inhibit is switched.
• Switch on mains supply or ensure sufficient supply via
DC bus.
• Adjust setting in
C00142
if required.