Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
L
417
8400 StateLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
An01: AIN1_I < 4 mA [xx.0125.00001]
CE04: MCI communication error [xx.0127.00002]
CE0F: MCI control word [xx.0127.00015]
CE4: CAN bus off [xx.0131.00000]
CA06: CAN CRC error [xx.0131.00006]
Response
(Lenze setting printed in bold)
Setting:
C00598/1
(
;
Adjustable response)
;
0: No Reaction
;
1: Fault
;
2: Trouble
:
3: TroubleQuickStop
4: WarningLocked
;
5: Warning
6: Information
Cause
Remedy
Open-circuit monitoring for analog input 1 has tripped.
• Only if the analog input has been configured as a
current loop of 4 ... 20 (
C00034/1
= 2).
• Check wiring of the analog X3/A1I input terminal for
open circuit.
• Check minimum current values of the signal sources.
Response
(Lenze setting printed in bold)
Setting:
C01501/1
(
;
Adjustable response)
:
0: No Reaction
;
1: Fault
;
2: Trouble
;
3: TroubleQuickStop
;
4: WarningLocked
;
5: Warning
;
6: Information
Cause
Remedy
Communication error with extension module in slot 1.
• Eliminate EMC interference.
• Switch off controller, correctly plug in the module,
switch on the controller again.
• Mains switching or restart of the controller,
respectively.
• Replace module/controller.
• If the problem occurs again, you needs to consult
Lenze.
Response
(Lenze setting printed in bold)
Setting:
C00594/2
(
;
Adjustable response)
;
0: No Reaction
:
1: Fault
;
2: Trouble
;
3: TroubleQuickStop
4: WarningLocked
;
5: Warning
6: Information
Cause
Remedy
Bit 14 ("SetFail") of the wMciCtrl control word of the
LS_DriveInterface
system block has been set.
Trace back signal source on the bus (e.g. PROFIBUS) that
sets bit 14 ("SetFail").
Response
(Lenze setting printed in bold)
Setting:
C00592/2
(
;
Adjustable response)
:
0: No Reaction
;
1: Fault
;
2: Trouble
;
3: TroubleQuickStop
;
4: WarningLocked
;
5: Warning
;
6: Information
Cause
Remedy
CAN on board
: "Bus off" status
• Received too many faulty telegrams.
• Damaged cable (e.g. loose contact).
• Two nodes have the same ID.
• Check wiring and bus terminating resistor.
• Set identical baud rate for each bus node.
• Assign different IDs to nodes.
• Eliminate electrical interference (e.g. EMC).
Response
(Lenze setting printed in bold)
Setting:
C00592/1
(
;
Adjustable response)
:
0: No Reaction
;
1: Fault
;
2: Trouble
;
3: TroubleQuickStop
;
4: WarningLocked
;
5: Warning
;
6: Information
Cause
Remedy
CAN on board
: A faulty CAN telegram has been detected. • Check wiring and bus terminating resistor.
• Eliminate electrical interference (e.g. EMC).