Sicherheitshinweise
Sicherheitshinweise für die Installation nach UL
19
EDK82EV222 DE/EN/FR 13.0
Sicherheitshinweise für die Installation nach UL
Warnings!
ƒ
Motor Overload Protection
–
For information on the protection level of the internal overload protection for a
motor load, see the corresponding manuals or software helps.
–
If the integral solid state motor overload protection is not used, external or
remote overload protection must be provided.
ƒ
Branch Circuit Protection
–
The integral solid state protection does not provide branch circuit protection.
–
Branch circuit protection has to be provided externally in accordance with
corresponding instructions, the National Electrical Code and any additional codes.
ƒ
Please observe the specifications for fuses and screw−tightening torques in these
instructions.
ƒ
E82xV251K
2
C ... E82xV222K
2
C (0.25 kW ... 2.2 kW, 240 V devices):
–
Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 240 V maximum, when protected by fuses or circuit
breakers.
–
Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 240 V maximum, when protected by CC, J, T or R class
fuses.
–
Shall be installed in a Pollution Degree 2 macro−environment.
–
Maximum surrounding air temperature: 0 ... +55 °C
–
> +40 °C: reduce the rated output current by 2.5 %/°C
–
Use 60/75 °C or 75 °C copper wire only.
ƒ
E82xV551K
4
C ... E82xV222K
4
C (0.55 kW ... 2.2 kW, 400/500 V devices):
–
Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 500 V maximum, when protected by fuses or circuit
breakers.
–
Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum, when protected by CC, J, T or R class
fuses.
–
Shall be installed in a Pollution Degree 2 macro−environment.
–
Maximum surrounding air temperature: 0 ... +55 °C
–
> +40 °C: reduce the rated output current by 2.5 %/°C
–
Use 60/75 °C or 75 °C copper wire only.