Fault messages
160
EDK82EV222 DE/EN/FR 13.0
Remedy
Cause
Fault
PC
1)
Keypad
LU
−
DC−bus
undervoltage
Mains voltage is too low
Check mains voltage
Voltage in DC−bus connection is
too low
Check power supply module
400 V controller is connected to
240 V mains
Connect controller to correct mains
voltage
OC1
$
11
Short circuit
Short circuit
l
Search for cause of short circuit;
check motor cable
l
Check brake resistor and cable to
brake resistor
Capacitive charging current of
the motor cable is too high
Use shorter/low−capacitance motor
cable
OC2
$
12
Earth fault
A motor phase has earth contact
Check motor; check motor cable
Capacitive charging current of
the motor cable is too high
Use shorter/low−capacitance motor
cable
Deactivate earth−fault detection for
test purposes
OC3
$
13
Controller overload
during acceleration
or short circuit
Set acceleration time is too short
(C0012)
l
Increase acceleration time
l
Check drive dimensioning
Defective motor cable
Check wiring
Interturn fault in the motor
Check motor
OC4
$
14
Controller overload
during deceleration
Set deceleration time is too short
(C0013)
l
Increase deceleration time
l
Check dimensioning of the
external brake resistor
OC5
$
15
Controller overload
during steady−state
operation
Frequent and too long overload
periods
Check drive dimensioning
OC6
$
16
Motor overload
(I
2
x t overload)
Motor is thermally overloaded by
e.g.
l
impermissible continuous
current
l
Check drive dimensioning
l
frequent or too long
acceleration processes
l
Check setting of C0120