Commissioning
Parameter setting with E82ZBC keypad
Vector control
138
EDK82EV222 DE/EN/FR 13.0
Comment
Switch−on sequence
15.
Enter the motor data
See motor nameplate
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: Depending on the controller
Enter the value for the motor circuit
configuration (star/delta) selected!
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: Depending on the controller
Enter the value for the motor circuit
configuration (star/delta) selected!
E
Motor cos
j
(C0091)
Lenze setting: Depending on the controller
16.
Start the motor parameter identification (C0148)
Only when the motor is cold!
A
Ensure that the controller is inhibited
Terminal X3/28 = LOW
B
Set C0148 = 1
Press
C
Enable the controller
l
Terminal X3/28 = HIGH
l
The identification starts:
– Segment
is off
– The motor consumes current and
makes a high−pitched" tone.
– The motor does not rotate!
D
If segment
becomes active again after approx. 30 s,
inhibit controller again.
l
Terminal X3/28 = LOW
l
Identification is completed.
l
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance (C0092)
l
Measured and stored:
– Motor stator resistance (C0084) = Total
resistance of motor cable and motor
17.
If necessary, select more parameters
Activate e.g. JOG frequencies (C0037, C0038,
C0039) or motor temperature monitoring
(C0119)
When all settings are complete:
18.
Select setpoint
E.g. via potentiometer at terminals 7, 8, 9
19.
Enable the controller
Terminal X3/28 = HIGH
20.
The drive is now running.
If the drive does not start, additionally press