Technical data
General data and operating conditions
101
EDK82EV222 DE/EN/FR 13.0
Ambient conditions
Climatic conditions
Storage
IEC/EN 60721−3−1
1K3 (−25 ... +60 °C)
< 6 months
1K3 (−25 ... +40 °C)
> 6 months
> 2 years: form the DC bus
capacitors
Transport
IEC/EN 60721−3−2
2K3 (−25 ... +70 °C)
Operation
2.2 ... 11 kW
IEC/EN 60721−3−3
3K3 (−10 ... +55 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.
15 ... 90 kW
3K3 (0 ... +50 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.
Pollution
IEC/EN 61800−5−1
Degree of pollution 2
Site altitude
< 4000 m amsl
> 1000 m amsl: reduce the rated output current by 5 %/ 1000 m.
Electrical
AC mains connection
Max. mains voltage range
E82xV251K2... and E82xV371K2...
1/N/PE 180 V − 0 % ... 264 V + 0 %
E82xV551K2... to E82xV752K2...
1/N/PE 180 V − 0 % ... 264 V + 0 % or
3/PE 100 V − 0 % ... 264 V + 0 %
E82xV551K4... to E82xV903K4...
3/PE 320 V − 0 % ... 550 V + 0 %
Mains frequency
45 Hz − 0 % ... 65 Hz + 0 %
Mains system
With earthed neutral (TT, TN): unrestricted operation permitted
Other mains systems: observe restrictions described in the
system manual, chapter about project planning
Operation on public
supply systems
EN 61000−3−2
Limitation of harmonic currents
Total power drawn from the
mains
Compliance with the
requirements
1)
< 1 kW
With mains choke.
> 1 kW
Without additional measures.
1)
The additional measures described only ensure that the controllers comply
with the requirements of EN 61000−3−2. Compliance of the machine/system
with the requirements is in the responsibility of the machine/system
manufacturer!