Electrical installation
Wiring
EMC−compliant wiring
119
EDK82EV222 DE/EN/FR 13.0
Realisation
M
3~
PES
L < 500 mm
L < 40 mm
PE
PE
PE
8
9
PES
PES
1
2
3
4
5
6
7
0
8200vec008
Mounting plate with electrically conductive surface
Control cable to the function module, connect the shielding to the EMC shield sheet (PES) with a surface as large
as possible
2−pole terminal for motor PE and motor shield
PE of the motor cable
Shield of the motor cable
Shielded motor cable, low−capacitance
(Core/core 1.5 mm
2
£
75 pF/m; from 2.5 mm
2
£
100 pF/m; core/shield
£
150 pF/m)
Shielded PTC cable or thermal contact cable
Connect the cable shields to the EMC shield sheet (PES) with a surface as large as possible. Use the supplied
shield clamps.
Star or delta connection as indicated on the motor nameplate
EMC cable connector (not included in the delivery package)