Troubleshooting and fault elimination
Fault elimination
Fault messages
159
EDK82EV222 DE/EN/FR 13.0
Remedy
Cause
Fault
PC
1)
Keypad
ce6
$
67
System bus (CAN)
function module on
FIF has the
"Warning" or
"BUS−OFF" status
(configurable in
C0126)
CAN controller reports "Warning"
or "BUS−OFF" status
l
Check bus termination
l
Check shield connection of the
cables
l
Check PE connection
l
Check bus load, reduce the baud
rate, if necessary
ce7
$
68
Communication
error during remote
parameterisation
via system bus
(C0370)
(configurable in
C0126)
Node does not respond or is not
available
l
Check bus termination
l
Check shield connection of the
cables
l
Check PE connection
l
Check bus load, reduce the baud
rate, if necessary
For operation with application
I/O:
Parameter set change−over has
been parameterised incorrectly
The "parameter set change−over"
signal (C0410/13, C0410/14) must be
connected to the same source in all
paramerter sets
EEr
$
91
External fault
(TRIP−SET)
A digital signal assigned to the
TRIP−Set function is activated
Check external encoder
ErP0
...
ErP19
$
−
Communication
abort between
keypad and
standard device
Various
Contact Lenze
FAn1
$
95
Fan failure
(only 8200 motec
3 ... 7.5 kW)
TRIP or warning
configurable in
C0608
Fan is defective
Replace fan
FAn1
−
Fan is not connected
Connect fan
Check wiring
H05
$
105
Internal fault
Contact Lenze
id1
$
140
Faulty parameter
identification
Motor is not connected
Connect motor
LP1
$
32
Motor phase error
(display when
C0597 = 1)
l
Failure of one/several motor
phases
l
Motor current is too low
l
Check motor supply cables
l
Check V
min
boost,
l
Connect motor with a
corresponding power or adapt
motor with C0599
LP1
182
Motor phase error
(Display when
C0597 = 2)