Commissioning
Parameter setting with the XT EMZ9371BC keypad
Vector control
143
EDK82EV222 DE/EN/FR 13.0
Comment
Switch−on sequence
14.
Start the motor parameter identification (C0148)
Only when the motor is cold!
A
Ensure that the controller is inhibited
Terminal X3/28 = LOW
B
Set C0148 = 1
Press
C
Enable the controller
l
Terminal X3/28 = HIGH
l
The identification starts:
– Segment
is off
– The motor consumes current and makes a
high−pitched" tone.
– The motor does not rotate!
D
If segment
becomes active again after approx. 30 s,
inhibit controller again.
l
Terminal X3/28 = LOW
l
Identification is completed.
l
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance (C0092)
l
Measured and stored:
– Motor stator resistance (C0084) = Total
resistance of motor cable and motor
15.
Activate the motor temperature monitoring (C0119) if you
have connected a PTC or thermal contact to terminal X2.2
Lenze setting: switched off
Possible settings
(
When all settings are complete:
16.
Select setpoint
E.g. via potentiometer at terminals 7, 8, 9
17.
Enable the controller
Terminal X3/28 = HIGH
18.
The drive is now running.
If the drive does not start, additionally press