User Manual for ELD5 Servo
(V1.00)
www.leadshine.com
70
No
Parameter
Name
input
Setup value
Unit
1
PA_001
Control mode setup
/
22
/
2
PA_312
Acceleration time setup
/
User-specified
millisecond
3
PA_313
Deceleration time setup
/
User-specified
millisecond
4
PA_314
Sigmoid acceleration/deceleration time
setup
/
User-specified
millisecond
5
PA_315
Zero-clamp function selection
/
0
/
6
PA_319
Torque command direction input gain
/
User-specified
0.1V/100%
7
PA_320
Torque setup input reversal
/
User-specified
/
8
PA_321
Speed limit value 1
/
User-specified
R/min
9
PA_400
SI1 input selection
Srv_on
hex:030000
/
10
PA_422
Analog input offset setup
/
User-specified
0.359mv
11
PA_423
Analog input filter
/
User-specified
0.01ms
◆
Wiring Diagram
◆
Operation Steps
1. connect terminal CN1.
2. Enter the power (DC12V to 24V) to control signal (the COM + and COM-).
3. Enter the power to the driver.
4. Confirm the value of the parameters, and write to the EEPROM and turn off/on the power (of the driver)
5.Connect the Srv_on input to bring the driver to servo-on status and energize the motor.
6. apply DC voltage between torque command input , VIN+ and VIN-, and gradually increase from 0V to
confirm the motor runs.
7.
Check the motor torque at monitor mode ("
" ), Whether actual torque is as per the setup or not
8.
When you want to change the torque magnitude, direction and velocity limit value against the command
voltage, set up the following parameters :
Pr3.19. Pr3.20. Pr3.21
If the motor does not run correctly, refer to the Factor of No-Motor running in data monitor mode
("
" ).
7.3 Automatic Control Mode Run
7.3.1 Operation Mode Selection
ELD5 series Low-voltage AC servo drives support the position, speed, torque three basic modes of operation,
and can switch freely between the three basic modes of operation by switch or modify parameters.