User Manual of EL6-CAN AC Servo
www.leadshine.com
80
Velocity is 0
0
Velocity is not equal 0
0
Velocity is equal 0
6.6.3 Related objects
Object Dictionary
Description
Setup value
Units
6060H
Mode of operation
3
6040H
Controlword
6041H
Statusword
60FFH
Target velocity
Pulse /s
6083H
Profile acceleration
Pulse /s
2
6084H
Profile deceleration
Pulse /s
2
606CH
Velocity actual value
Pulse /s
606BH
Velocity demand value
Pulse /s
6.6.4 Example of profile velocity mode
No
Command
Function
1
81
00
00 00 00 00 00 00
Reset all nodes. If you need to reset the specified node, the node
number is changed by modifying the two digits after 81 (note that
it is hexadecimal)
2
01
00
00 00 00 00 00 00
Start remote control for all nodes. If remote control of the
specified node needs to be started, the node number is changed by
modifying the two-digit number after 01 (note that it is
hexadecimal).
3
2b
40 60
00 06 00 00 00
Write control word as 06
H
,
state machine switching status
Switch On Disabled->Ready to Switch On
4
2b
40 60
00 07 00 00 00
Read control word as 07H
,
state machine switching status
Ready to Switch On-> Switched On
The relay in the actuator is engaged at this point
5
2b
40 60
00 0f 00 00 00
Write control word as 0fH
,
state machine switching status
Switched On->Operation Enable. Servo-Enabled
6
2f
60 60
00 03 00 00 00
Write operation mode as 3H, profile velocity mode
7
23
83 60
00 90D0 03 00
Write the protocol acceleration as 3D090H
(1500rpm/s, 10000p/r)
8
23
ff 60
00 90 D0 03 00
Write the protocol speed as 3D090H
(1500rpm, 10000p/r )
9
2b
40 60
00 07 00 00 00
Write control word as 07H,state machine switching status
Operation Enable -> Switched On. Servo-Disabled
10
2b
40 60
00 06 00 00 00
Write control word as 06H,state machine switching status
Switched On ->Ready to Switch On
Notes: The COB-ID of step 1 (reset node) and step 2 (start node) is "0x000", and the COB-ID of the remaining
steps is the address 0x600 + Node ID