Operating Manual
79
© Copyright 2016
OMBG3000 – Rev1
0x0064
Alarm 2
1=Triggered,
0x0066
Alarm 3
2=Triggered and in recovery zone
0x0068
Alarm 4
4 = Latched
0x006A
Alarm 5
8 = Muted
0x006C
Alarm 6
9 = Triggered alarm and muted
0x006E
Alarm 7
A = Recovering alarm and muted
0x0080
Current sample Point
1 to 4
The Profinet module updates the readings from the BIOGAS 3000 every 2.5
seconds.
Successful communication between the Modbus output and the Profinet
module is indicated by the subnet status light ‘5’ on the module showing
green. If for any reason the communications is intermittent or fails, the light
flashes red or is permanently red, and the value being read is cleared to zero
and not frozen with a previous value. Monitoring for an example the year,
month and day for non-zero values will gain confidence that communications is
ongoing.
4.15
Heater Option
If purchased at the point of sale, the equipment will be fitted with a 100W
heater (suitable for the relevant mains input voltage), control thermostat, and
enclosure insulation. The thermostat is pre-set to 15°C (59⁰F) and cannot be
adjusted.