64
Operating Manual
OMBG3000 – Iss.01
© Copyright 2016
Figure 8 - Profibus module switch location
Figure 9 - Profibus module switch identification
In addition, the Modbus port on the BIOGAS 3000 must be configured as
followed:
Node Address
1
Baud Rate
9600
Parity
Even
Stop Bits
1
Termination
On
The BIOGAS 3000 acts as a slave.
To configure the Modbus port on the BIOGAS 3000, refer to section