89
8
System Operation
Fault
Code
No.
Restart according to
Description
TRD
EN676
103
0
0
Internal fault: Error in misc. data
H/Ü
The fault can occur during an internal self-test. A fault was discovered during the
reading of the redundant data in the EEPROM.
Reset the fault. In the process, switch the mains voltage off and on again if neces-
sary.
Check all fuses in the device.
Re-enter the curve.
Import the current data record into the device using the remote control software and
check this data record.
If the fault persists despite reset
the EEPROM is possibly defective:
Exchange the EEPROM.
Import the current data record into the device using the remote control software and
check this data record.
104
0
0
Internal Fault: D/A-Converter faulty
H
Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If the fault message continues to persist
exchange the device or respective card.
Summary of Contents for VMS 4
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...