Commissioning
6.5.5
Programming While The Burner Is Stationary
NOTICE
The monitoring values may clearly deviate from the values of the main processor, depending
on the configuration (redundant signals or not). It is essential that the actual value matches
the setpoint value of the respective processors, not the correspondance of values between
the processors.
NOTICE
Should there be any redundant feedbacks, the curves must be programmed on a burner
during operation.
Turn selector switch (1) to SETPOINT
Switch (4) up or down
until system is optimally adjusted at instantaneous firing
rate
on VMS 5
setpoint and actual value feedback are displayed
Switch (4) Channel 2 up or down until channel 5 is
optimally adjusted
Turn selector switch (1) to ACTUAL VALUE FEED-
BACK
the display shows the value of the external
feedback.
at the three-point-step channel the display shows
the same value as in the setpoint setting.
Press ENTER (3)
SZP-POINT appears on the display.