49
6
Commissioning
Parameter 896 can be used to select whether the pre-setting is always (at each firing rate
change) to be activated (factory setting Standard 1), or not activated (content 2).
Furthermore, the updating too can be turned off. It is then possible to select whether, at firing
rate changes, the neutral correction value or the ’Base value without controller’ is to be output
(parameter 896). The overshoot becomes active again when updating is turned off.
6.6.2.2 Extended Control Strategy (Air Shortage)
Regardless of the selected control strategy and the lag time set (parameter 898/900), imme-
diate and extensive action is taken by the controller to combat any air shortage occurring. The
objective is to avoid air shortage and to correct any such shortage as quickly as possible.
Controller overshooting and the resulting excess air are accepted as unavoidable.
Summary of Contents for VMS 4
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...