Commissioning
6.5.10 Adding Points
Should there be a previously saved curve that does not contain twenty points, additional points
may be added.
NOTICE
Up to 20 points can be programmed. A high resolution should also be used, since this ensures
precise combustion control. It is also possible, however, to store fewer than 20 points. This is
advisable, for example when entering an initial, approximate curve.
NOTICE
A definitive curve for the VMS should always comprise at least 10 points.
Turn selector switch (2) to SETTINGS
Turn selector switch (1) to FIRING RATE RATING (fir-
ing rate)
Run to desired firing rate
If the display shows a flashing number after the firing-
rate rating, instead of adding a new point an old one is
overwritten.
Turn selector switch (1) to SETPOINT
Switch (4) up or down until system is optimally adjusted
at the selected firing-rate rating.
VMS 5: Switch (1) to DISPLAY CHANNEL 5
the display shows setpoint and actual value feed-
back
Switch (4) channel 2 up or down until channel 5 is opti-
mally adjusted.
Turn selector switch (1) to ACTUAL VALUE FEED-
BACK
Wait until feedback has stopped.
Press ENTER (3)
Point X (number of the new firing rate rating appears
on the display, if 6 points have previously been entered,
’Point 7’ appears, only then is it classified according to
its value)
if necessary add further values
otherwise store
note monitoring values
Summary of Contents for VMS 4
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...