72
6
Commissioning
6.8.6
Protocol Example
Date:
Serial No.:
Installation:
Operating mode:
Tolerance on air shortage side:
Channel Functions
Dead band
Monitoring Band
Band shift
Channel 1
356
32 /34
62 / 67
708
Channel 2
357
33 / 43
63 / 73
709
Channel 3
358
34 / 35
64 / 74
710
Channel 4
359
35 / 45
65 / 75
711
Channel 5
360
36 / 46
66 / 76
712
Adjustment in
air deficiency
direction
Adjustment in
excess air
direction
Correction
range
Correction value
with O
2
trim deac-
tivated
correction value
with air deficiency
(cross out, if not applicable)
1.
The dead band on the air shortage side is always 0 digit
2.
The band shift is at least as large as the monitoring band in the air deficiency direction.
3.
If the combustion air fan has speed control, the monitoring band on the air deficiency side is 0 digits.
4.
The following applies if 1. and 2. and, if applicable, 3. are satisfied: there is no tolerance on the air shortage side, therefore
the shut-off limits in the air shortage direction do not have to be tested.
5.
A test has not been performed with regard to excess air because
..........................................................................................................................................................................
*
6.
It should be ensured that, if the O
2
controller is deactivated, the burner is operated with more excess air than when operat-
ing onthe required value curves (corresponding to the burner setting protocol)
I have checked the facts above.:......................................................................................................................................................
company name date signature
*
If this phrase has been deleted a test protocol on the shut-off limits for excess air should be submitted.
Summary of Contents for VMS 4
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...