58
6
Commissioning
6.6.5.10 What Additional Modes mean
op
O
2
trim on standby (during burner start-up), or
O
2
trim temporarily switched off by parameters
914 and 915, depending on firing rate.
or
O
2
trim active
ot
O
2
trim temporarily deactivated (air shortage,
probe dynamics etc).
od
O
2
trim deactivated (in fault), e.g. test routines
failed during burner start-up, dynamic test nega-
tive, O
2
trim temporarily deactivated for over 1
hour etc.