21
4
Settings
4.3
Parameter
4.3.1
Parameter Settings
The parameter level can be accessed by turning to the ’Parameter’ selector switch position.
When working on level 1 ... 4, this works only with the burner stationary (i.e. no signal on the
digital inputs). Only level 0 is accessible with the burner running.
NOTICE
As a rule, the factory parameter settings are precisely tuned for the installation for which the
unit has been designed. Therefore, it is only necessary to change parameter settings in ex-
ceptional cases.
4.3.2
Access Levels
The parameters are divided into four different access levels according to function and safety
classification:
•
Operating level (Level 0)
Accessible without password, non-critical parameters that may possibly have to be altered
during operation.
•
Customer level (Level 1)
Accessible with modifiable password (on delivery set at ’0000’), access to parameters, ad-
justment of which calls for technical knowledge, which are tailored to the system and
which are not altered during operation.
•
Service level (Level 2)
Accessible with a fixed password, but only to personnel specially trained in parameterisa-
tion. Access to all parameters that are not fixed on the basis of standards and technical
regulations.
•
Production levels (Level 3 and 4)
Access to all parameters (only possible through LAMTEC)
Each parameter level is protected by its own checksum. This checksum serves to show that
no changes have been made.
Summary of Contents for VMS 4
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...