35
6
Commissioning
Potentiometer adjustment values (approximate)
6.5
Programming of Curves
6.5.1
Programming of Fuel/Air Ratio Control
NOTICE
Final programming of the unit with the burner stationary can only be done when it is certain
that all feedback signals are present in the same way as when the burner is in operation (e.g.
not temperature-dependent or active speed feedback). Otherwise programme when burner is
in operation.
NOTICE
Programming can only be performed with specified modes. Otherwise the unit registers a fault
and will accept no inputs. It may be necessary to wait for the automatic combustion sequence
control to release the control before programming when the burner is in operation (via mode
’EV’, ’EZ’, ’EG’).
If burner locks out whilst programming in process e.g. owing to control shut-off
see chapter
8.1.4 Proceed with Programming
If FMS skips to ’ES’ mode whilst programming is in progress
see chapter
8.1.4 Proceed with Programming
Pot
Lower stop
*
*
provided that potentiometer r.p.m. range is fully utilised
Upper stop *
5 k
Ω
80
920
1 k
Ω
200
800
Select fuel
either with stationary burner
Signal on terminal 2 (BURNER ON)
or
with burner in operation:
Signal on terminal 2 (boiler thermo-
stat)
Wait until burner is on
= 0 Display AU
= 1
Summary of Contents for VMS 4
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...