34
F28
Function enabled
if F26 = ON
OFF*
In interlock function, the opening control on the closed door is not saved. Please refer to the
paragraph "Interlock system".
ON
In interlock function, the opening command on the closed door is saved and the subsequent
opening will take place as soon as the other door will be closed.
Please refer to the paragraph "Interlock system".
F29
Function enabled
if F26 = ON
OFF*
Standard operation of the electric lock in the interlock system.
ON
Electric lock disabled if the 2 doors are closed in the automatic programs.
Refer to the paragraph “Interlock system → Interlock application with electric locks disabled
with closed doors”.
F30
Not used
F31
OFF*
The internal and external radars are not active during the closing movement in the work
program “Night Lock”
ON
The internal and external radars are active during the closing movement in the “Night Lock”
work program, therefore the door is re-opened.
F32
OFF*
The F1 button of the selector ET‑DSEL or the button B of the selector T‑NFC controls door
opening in automatic programs only.
ON
The F1 button of the selector ET‑DSEL or the button B of the selector T‑NFC controls door
opening both in automatic and in NIGHT LOCK programs.
F33
1
OFF
Single leaf door (display only, for editing it is necessary to repeat the setup).
ON
Double leaf door (display only, for editing it is necessary to repeat the setup).
F34
1
OFF
Master automation in double-leaf door (display only, for editing it is necessary to repeat the
setup).
ON
Slave automation in double-leaf door (display only, for editing it is necessary to repeat the
setup).
F35
OFF*
For double-leaf door: after a power failure, during the first opening movement the leaves start
at the same time.
ON
For double-leaf door: after a power failure, during the first opening movement the leaves start
respecting the offset.
F36m
Multiple selection
function
Multiple selection function, allowing to set the position of the manual or mechanic program
selector where the pedestrian opening function of only the master leaf in a dual-leaf door is
enabled.
A*
Pedestrian opening DISABLED.
B
Pedestrian opening in position “Manual free door”.
C
Pedestrian opening DISABLED.
D
Pedestrian opening in “Night Lock” position.
F38
1
OFF
The closing manoeuvre is carried out with the sole power of the spring.
S
ON
The closing manoeuvre is carried out with the activation of the motor as aid to the spring
(draughts or other unfavourable situations).
F39
Not used
F40
OFF*
Not used
ON
The button F2 of the digital selector ET-DSEL or T-NFC disables the step by step function set
by the potentiometer F18 = ON.
F41m
Multiple selection
function
Multiple selection function that allows to set the mode of operation of the open collector output
between the terminals S-24.
WARNING! If you have selected the interlock function → F26=ON the open collector output
S-24 operates as interlock signal and all the functions provided for by F41m are automatically
disabled.
S
A*
Door state signal. The output turns on when the door is moving, whereas it turns off when
the door is closed.
B
Battery state. The activation of the output reports the status of damaged battery.
C
Maintenance signal
The output activates when the door reaches the number of cycles provided for by the
maintenance plan set by the potentiometer P48.
D
The output is enabled in the automatic programs and is disabled in night lock.
E
Not used
F
Not used
G
Not used
H
Not used