
4 Valve Description
27 of 100
4.3.4 ECOLINE GLV 150-300
4.3.4.1 Operating data
Table 21: Operating properties
Characteristic
Value
Nominal pressure
Class 150 - 300
Nominal size
NPS 2'' - 12''
Max. permissible pressure
50 bar / 720 PSI
Min. permissible temperature
0 °C / 32 °F
Max. permissible temperature
816 °C / 1500 °F
Temperatures < 0 °C on request
Selection as per pressure/temperature ratings
(
ð
Section 4.3.4.4, Page 29)
4.3.4.2 Fluids handled
▪
Steam
▪
Gas
▪
Fluids containing gas
▪
High-temperature hot water
▪
Fluids containing mineral oils
▪
Oil
▪
Feed water
Summary of Contents for ECOLINE FYC
Page 4: ...Contents 4 of 100 9 5 EU Declaration of Conformity for ECOLINE GLB 150 600 95 Index 96...
Page 98: ......
Page 99: ......