4 Valve Description
14 of 100
4.3 Globe Valves to ANSI/ASME with Gland Packing
4.3.1 ECOLINE GLC 150-600
4.3.1.1 Operating data
Table 5: Operating properties
Characteristic
Value
Nominal pressure
Class 150 - 600
Nominal size
NPS 2'' - 12''
Max. permissible pressure
106 bar / 1500 PSI
Min. permissible temperature
0 °C / 32 °F
Max. permissible temperature
816 °C / 1500 °F
Temperatures < 0 °C on request
Selection as per pressure/temperature ratings
(
ð
Section 4.3.1.4, Page 16)
4.3.1.2 Fluids handled
▪
Steam
▪
Fluids containing gas
▪
Fluids containing mineral oils
▪
Gas
▪
High-temperature hot water
▪
Feed water
▪
Oil