Caution
Amaprop
R
19
Adjust the feet so that the guide rail is in perfectly vertical
position; note the jet direction.
Vertical alignment of guide rail using a spirit level
After alignment, secure the M16x55 bolts connecting the
braces with the feet using Loctite and tighten to 150 Nm with a
torque wrench. Do not forget to fit the lock nuts!
Secure the bolted connections between the braces or
prefabricated bracing and the pump bracket with Loctite and
tighten to the below torques with a torque wrench. Do not forget
to fit the washers and lock nuts!
Amaprop
1200-1801
M16x70
Tightening torque
168 Nm
Mark out and drill the holes for the composite anchor bolts. Drill
bit diameter 18 mm; bore depth 125 mm. Even level foundation
floors have site--related tolerances. Therefore, the 4 holes for
the feet should only be drilled when the feet rest fully on the tank
floor (use slotted holes to adjust)! The hole pattern data for the
composite anchor bolts (dimensions F
A
, F
B
, F
C
) are for
orientation only; it is important that the feet rest fully on the floor!
Observe the installation instructions for the composite anchor
bolts given in section 3.1.
Note:
Fill any remaining gaps under the foot plate with UPAT chemical
mortar (see section 7.8).
Observe
the
manufacturer’s
application
instructions
(supplementary sheet)!
The mortar can only be applied when the tank is empty and dry.
Do not apply if there is still some minimal water level in the tank
(rainfall). The mortar cannot be applied by divers.
Any unfilled gaps remaining will result in
increased stresses on the composite anchor
bolts.
This may damage the composite anchor bolts, the mixer and
the installation parts.
Inadequate filling of any gaps remaining can invalidate any
liability of the manufacturer for consequential damage.
Drill a hole with Ø 18 mm and clean it (e.g. with compressed air).
Verify bore depth (125 mm).
Summary of Contents for Amaprop 1200
Page 38: ...AmapropR...
Page 39: ...AmapropR...