Function parameter list
-36-
Function
code
Name
Description
Default Modify
P00.10
Frequency
set through
keypad
When A and B frequency commands
select the keypad for setting, the value of
the function code is the original setting
one of the frequency data of the VFD.
Setting range: 0.00 Hz–P00.03 (Max. output
frequency)
50.00Hz
○
P00.11 ACC time 1
ACC time means the time needed if the
VFD speeds up from 0Hz to the max.
output frequency (P00.03).
DEC time means the time needed if the
VFD speeds down from the max. output
frequency (P00.03) to 0Hz.
The VFD has four groups of ACC/DEC time,
which can be selected by P05. The factory
default ACC/DEC time of the VFD is the
first group.
Setting range of P00.11 and P00.12:
0.0–3600.0s
Model
depended
○
P00.12 DEC time 1
Model
depended
○
P00.13
Running
direction
0: Runs at the default direction, the VFD
runs in the forward direction. FWD/REV
indicator is off.
1: Runs at the opposite direction, the VFD
runs in the reverse direction. FWD/REV
indicator is on.
Modify P00.13 to shift the rotation
direction of the motor. This effect equals to
the shifting the rotation direction by
adjusting either two of the motor lines (U,
V and W). The motor rotation direction
can be changed by QUICK/JOG on the
keypad. Refer to parameter P07.02 for
details.
Note:
When the function parameter comes
back to the default value, the motor’s
running direction will come back to the
factory default state. In some cases it
should be used with caution after
commissioning if the change of rotation
direction is disabled.
0
○