Ecowatt
®
Drive K120 series
Function parameter list
-58-
Function
code
Name
Description
Default Modify
P04.07
V/F
frequency
point 3 of
motor 1
b
f
Output voltage
f1
f2
f3
V1
V2
V3
b
V
%
100
Output
frequency
Hz
Setting range of P04.03: 0.00Hz –P04.05
Setting range of P04.04: 0.0%–110.0% (of rated
voltage of motor 1)
Setting range of P04.05: P04.03 –P04.07
Setting range of P04.06: 0.0%–110.0% (of rated
voltage of motor 1)
Setting range of P04.07: P04.05–P02.02 (rated
frequency of motor 1) or P04.05– P02.16 (rated
frequency of motor 1)
Setting range of P04.08: 0.0%–110.0% (of rated
voltage of motor 1)
00.00Hz
○
P04.08
V/F
voltage
point 3 of
motor 1
00.0%
○
P04.09
V/F slip
compensat
ion gain of
motor 1
The function code is used to compensate for
the motor rotating speed change caused by
load change in the space voltage vector
mode, and thus improve the rigidity of the
mechanical characteristics of the motor. You
need to calculate the rated slip frequency of
the motor as follows:
△
f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the
motor, corresponding to function code P02.02.
n is the rated rotating speed of the motor,
corresponding to function code P02.03. p is
the number of pole pairs of the motor. 100.0%
corresponds to the rated slip frequency
△
f of
motor.
Setting range: 0.0–200.0%
100.0%
○
Summary of Contents for Ecowatt Drive K120 Series
Page 1: ......
Page 170: ...Ecowatt Drive K120 series Optional peripheral accessories 163 PB External braking resistor VFD...
Page 172: ......
Page 173: ......