Function parameter list
-34-
Function
code
Name
Description
Default Modify
terminals. The VFD provides 1 high speed
pulse input as the standard configuration.
Range of pulse frequency: 0.00–50.00kHz.
100.0% of the high speed pulse input
setting corresponds to the max. output
frequency (P00.03) in forward direction
while -100.0% corresponds to the max.
output frequency in reverse direction
(P00.03).
Note:
The pulse setting can only be input
by multi-function terminals HDI. Set
P05.00 (HDI input selection) to "High speed
pulse input" and P05.49 (HDI high-speed
pulse input function selection) to
"Frequency setting input".
5: Simple PLC program
The VFD runs at simple PLC program
mode when P00.06=5 or P00.07=5. Set P10
(Simple PLC and multi-step speed control)
to select the running frequency, running
direction, ACC/DEC time, and the keeping
time of corresponding step. See the
function description of P10 group for
detailed information.
6: Multi-step speed running
The VFD runs at multi-step speed mode
when P00.06=6 or P00.07=6. Set P05 to
select the current running step, and set
P10 to select the running frequency of the
current step.
The multi-step speed has the priority
when P00.06 or P00.07 are not equal to 6,
but the setting step can only be the 1–15
step. The setting step is 1–15 if P00.06 or
P00.07 equals to 6.
7: PID control
The running mode of the VFD is process