Ecowatt
®
Drive K120 series
Product overview
-7-
2.1.5
Basic commissioning
Complete the basic commissioning as follows before the actual use of the VFD:
1.
Autotuning. If possible, de-coupled from the motor load to start dynamic
autotuning. Or if not, static autotuning is available.
2.
Adjust the ACC/DEC time according to the actual running of the load.
3.
Commissioning the device via jogging and check that the rotation direction is as
required. If not, change the rotation direction by changing the wiring of motor.
4.
Set all control parameters and then operate.
2.2
Product specification
Function
Specification
Power input
Rated input voltage (V) 1PH 220V (-15%)–240V(+10%)
Rated input current (A) Refer to "Rated specifications".
Rated frequency
50Hz or 60Hz; allowed range: 47–63Hz
Power
output
Output voltage (V)
0–input voltage
Output current (A)
Refer to "Rated specifications".
Output power (kW)
Refer to "Rated specifications".
Output frequency (Hz) 0–400Hz
Technical
control
performance
Control mode
SVPWM, SVC
Motor type
Asynchronous motor and permanent magnet
synchronous motor
Speed regulation ratio
Asynchronous motor 1:100 (SVC), synchronous
motor 1:20 (SVC)
Speed control precision ± 0.2% (SVC)
Speed fluctuation
± 0.3% (SVC)
Torque response
< 20ms ( (SVC)
Torque control
precision
10%
Starting torque
Asynchronous motor: 0.5Hz/150% (SVC)
Synchronous motor: 2.5 Hz/150% (SVC)
Overload capacity
150% for 1 minute, 180% for 10 seconds, and
200% for 1 second.
Running
control
performance
Frequency setting
method
Settings can be implemented through keypad
digits, analog, pulse frequency, multi-step
speed running, simple PLC, PID, Modbus
communication, and so on.
Settings can be combined and the setting
channels can be switched.