Ecowatt
®
Drive K120 series
Product overview
-8-
Function
Specification
Automatic voltage
regulation
The output voltage can be kept constant
although the grid voltage changes.
Fault protection
Provide comprehensive fault protection
functions, such as protection against
overcurrent,
overvoltage,
undervoltage,
overtemperature, phase loss, and overload.
Speed tracking restart
Used to implement impact-free smooth startup
for rotating motors.
Peripheral
interface
Analog input
One input (AI2) 0–10V/0–20mA and 1 input
(AI3) -10–10V.
Analog output
Two inputs (AO1 and AO2) 0–10V/0–20mA.
Digital input
Four regular inputs; max. frequency: 1kHz;
One high-speed input; max. frequency: 50kHz
Digital output
One Y1 terminal output
Relay output
Two programmable relay outputs:
RO1A: NO; RO1B: NC; RO1C: common terminal;
RO2A: NO; RO2B: NC; RO2C: common terminal.
Contact capacity: 3A/AC250V
Others
Installation mode
Wall and rail installation for the 1PH 220V
(≤2.2KW) VFD models.
Wall and flange installation for the 1PH 220V
(4kW) VFD model.
EMI filter
1PH 220V (4kW) VFD model can satisfy the
requirements of IEC 61800-3 C3, other models
can satisfy the requirements of IEC 61800-3 C3
by installing optional external filter. The whole
series can satisfy the requirements of IEC
61800-3 C2 by installing optional external filter.
Temperature of running
environment
-10–+50°C; derating is required if the ambient
temperature exceeds 40°C.
Altitude
Below 1000m.
When the altitude exceeds 1000m, derate by 1%
for every increase of 100m.
When the altitude exceeds 3000m, consult the
local Kruger dealer or office for details.
Summary of Contents for Ecowatt Drive K120 Series
Page 1: ......
Page 170: ...Ecowatt Drive K120 series Optional peripheral accessories 163 PB External braking resistor VFD...
Page 172: ......
Page 173: ......