Ecowatt
®
Drive K120 series
Function parameter list
-101-
Function
code
Name
Description
Default Modify
P11.03
Overvoltage
stall
protection
0: Disable
1: Enable
Overvoltage
stall
threshold
Output
frequency
Time t
Time t
DC bus voltage V
1
○
P11.04
Overvoltage
stall
protection
voltage
110–150% (standard bus voltage) (380V)
130%
○
110–150% (standard bus voltage) (220V)
120%
P11.05
Current
limit
action
During accelerated running, as the load is too
large, the actual acceleration rate of motor is
lower than that of output frequency, if no
measures are taken, the VFD may trip due to
overcurrent during acceleration.
Ones place: Current limit action selection
0: Invalid
1: Always valid
Tens place: Hardware current limit overload
alarm selection
0: Valid
1: Invalid
01
◎
P11.06
Automatic
current
limit level
Current limit protection function detects
output current during running, and compares
it with the current-limit level defined by
P11.06, if it exceeds the current-limit level, the
VFD will run at stable frequency during
accelerated running, or run in decreased
frequency during constant-speed running; if
it
exceeds
the
current-limit
level
continuously, the VFD output frequency will
drop continuously until reaching lower limit
frequency. When the output current is
160.0%
◎
P11.07
Frequency
drop rate
during
current
limit
10.00Hz/s
◎