Ecowatt
®
Drive K120 series
Communication protocol
-144-
Function
Address
Data description
R/W
characteristics
0005H: Stop
0006H: Coast to stop
0007H: Fault reset
0008H: Jogging to stop
The command transmitted by the master is as follows:
Parameter
address
CRC check
VFD
address
Write
command
Forward
running
If the operation is successful, the following response is returned (same as the command
transmitted by the master):
Parameter
address
CRC check
VFD
address
Write
command
Forward
running
Example 2: Set the "Max. output frequency" of the VFD whose address is 03H to 100Hz.
Function
code
Name
Description
Default Modify
P00.03
Max.
output
frequency
Used to set the max. output frequency of
the VFD. Pay attention to the function
code because it is the foundation of the
frequency setting and the speed of
acceleration (ACC) and deceleration
(DEC).
Setting range: P00.04–400.00Hz
50.00Hz
◎
According to the number of decimals, the fieldbus scale of the "Max. output frequency"
(P00.03) is 100. Multiply 100 Hz by 100. The value 10000 is obtained, and it is 2710H in
the hexadecimal form.
The command transmitted by the master is as follows:
Parameter
address
VFD
address
Write
command
CRC check
Parameter data
If the operation is successful, the following response is returned (same as the command
transmitted by the master):