Message explanations
A-60
385585/C
RIO: Loop mon. error 4
Description:
Unknown loop monitoring error 4.
Possible
consequences:
Is a symptom of an unknown FW error in the RIO module.
Corrective
actions:
Note error data and operational information. Contact customer support.
RIO: Loop mon. error 5
Description:
Unknown loop monitoring error 5.
Possible
consequences:
Is a symptom of an unknown FW error in the RIO module.
Corrective
actions:
Note error data and operational information. Contact customer support.
RIO: Loop Power error
Description:
Error in external 24 V loop power. Outside legal range (18-32 V).
Possible
consequences:
The functional consequences are unpredictable. I/O-values may not be trusted.
Corrective
actions:
Check 24V loop power. Try to restart the RIO Module.
If this does not help, replace the module.
RIO: Loop Stuck
Description:
The measurements on the loop terminal connections for the actual channel
indicate that some external device is blocking the signal.
Possible
consequences:
The device connected to the actual channel might not operate as intended. If
signal is input, value is frozen to last valid input as long as alarm is active.
Corrective
actions:
Check physical loop/cabling.
RIO: Module configuration error
Description:
The RIO module has detected some discrepancy or illegal values in the general
part of the module configuration setup.
Possible
consequences:
The functional consequences are unpredictable. Therefore the RIO module will go
to Maintenance mode.
Consequently the alarm itself will go to normal state.