Message explanations
385585/C
A-55
Corrective
actions:
Note error data and operational information. Replace RIO module. Contact
customer support.
RIO: Configuration CRC error
Description:
The RIO module has wrong configuration and must be reconfigured.
Possible
consequences:
The RIO module is reconfigured by the active RCU master.
Corrective
actions:
Note message text and operational information.
Contact Customer Support if the alarm does not disappear after reconfiguration.
RIO: Critical temperature (restart required)
Description:
The temperature within the RIO module cabinet is so high that it is no longer
operational.
Possible
consequences:
The RIO module is not operational. All output values are zero and input is frozen.
Corrective
actions:
Ensure proper cooling. Try to restart the RIO Module. If this does not help, replace
the module.
RIO: Current feedback outside tolerance
Description:
The return signal from an analog output current signal is outside expected limits.
Possible
consequences:
The device being controlled by the actual output signal might not operate as
intended.
Corrective
actions:
Check physical loop/cabling.
RIO: Error in readback of AO test value (reset required)
Description:
A read back value for test of calibration of analog outputs indicates an error.
Possible
consequences:
All affected IO channels are marked with error, and if input, values are frozen to
last valid value until the problem is solved and a manual reset is activated.
Corrective
actions:
Check cabinet power and earth connections. Try to reset the RIO Module. If this
does not help, replace the module.
RIO: Function (opcode) is not in this revision/release
Description:
At RIO module initialisation, some operation code was not recognized by the FW.