51
Configuration
Real-time clock (CLOCK)
CLK:
FORMAT
24 h / 12 h
24 h
TIME hh/mm
00..23:00...59
12 h
TIME hh/mm
00...11:00...59
AM/PM:
DAY/MONTH
01...31/01...12
YEAR
2000...2099
Tag number (TAG)
(Input in text line)
___
Configuration
Choices
Default
Cleaning contact (WASH)
Selected in text line
WASH
PARSET A/B
WASH
WASH
WASH CYCLE
000.0...999.9 h
000.0 h
WASH TIME
0000...9999 SEC
0060 SEC
CONTACT
N/O, N/C
N/O
Parameter set (PARSET)
Select fixed parameter set (A)
or switch between A/B via
control input or manually in
measuring mode
PARSET FIX /
CNTR INPUT /
MANUAL
(fixed parameter
set A)